Magnetism and electromagnetism · Subtopic 4 of 4

Transformers

A transformer has two coils wound on a soft iron core. An alternating current in the primary coil makes a changing magnetic field that induces an alternating e.m.f. in the secondary. The voltages are in the same ratio as the turns: VpVs=NpNs\dfrac{V_p}{V_s}=\dfrac{N_p}{N_s}. Power stations step the voltage up for transmission so the current, and the energy wasted heating the cables, is small.

Cambridge 5054 Paper 1Cambridge 5054 Paper 2Cambridge 0625 Papers 2, 4Cambridge 0625 Papers 1, 3Edexcel 4PH1 Paper 1PEdexcel 4PH1 Paper 2P≈ 30 minRevision 5 · updated 2026-10-27
Section 1 of 14

Learning objectives

  • Describe the structure of a transformer and explain how it works.
  • Use VpVs=NpNs\dfrac{V_p}{V_s}=\dfrac{N_p}{N_s} and identify step-up and step-down transformers.
  • Use IpVp=IsVsI_pV_p=I_sV_s for an ideal transformer.
  • Explain why high voltages are used for transmission, using P=I2RP=I^2R.
Pause and think

Power stations generate electricity at about 25 00025\,000 V, transmit it at up to 400 000400\,000 V, and your home uses about 230230 V. Why not just send it at 230230 V all the way?

Section 2 of 14

Core idea

Start hereWhy pylons carry 400 000 volts

Power lines run at enormous voltages, then step down to 230 V in homes. Why bother? At high voltage the current is small, and heating losses in the cables depend on current squared.

The big idea

VsVp=NsNp\frac{V_s}{V_p}=\frac{N_s}{N_p}; ideal: VpIp=VsIsV_pI_p=V_sI_s. High-voltage transmission cuts I2RI^2R losses. Works only with a.c.

1. How it works

A step-up transformer
primary: 4 turns, 10 Vsecondary: 8 turns, 20 Vsoft iron core
Changing current in the primary makes a changing magnetic field in the core, which induces a voltage in the secondary. It only works with a.c.
Turns ratio
  1. a.c. in primary⇒changing field in core\text{a.c. in primary}\Rightarrow\text{changing field in core}
    Soft iron links both coils.
  2. e.m.f. per turn is the same in both coils\text{e.m.f. per turn is the same in both coils}
    Same changing field through each turn.
  3. VsVp=NsNp\frac{V_s}{V_p}=\frac{N_s}{N_p}
    Total e.m.f. ∝ number of turns.
d.c. gives no changing field, so no output.
Worked exampleA step-down transformer

230 V to 11.5 V; primary 2000 turns; Is=2I_s=2 A.

Goal
NsN_s; IpI_p.
Strategy
Ratio; power conservation.
  1. 11.5230=120\frac{11.5}{230}=\frac1{20}
    Voltage ratio.
  2. Ns=200020=100N_s=\frac{2000}{20}=100
    Same ratio for turns.
  3. Ip=11.5×2230=0.1 AI_p=\frac{11.5\times2}{230}=0.1\text{ A}
    VpIp=VsIsV_pI_p=V_sI_s.
Answer100100 turns; 0.10.1 A.
✓ CheckVoltage down 20×, current up 20× ✓.

2. Transmission

Power lost in cables vs transmission voltage (same power sent)
50100150200250300350400204060801000transmission voltage (kV)power lost (relative)loss ∝ 1/V²
Power lost =I2R=I^2R. Doubling the voltage halves the current and cuts the loss to a quarter. Hence the National Grid uses up to 400 000 V.
Worked example1 MW through 5 Ω cables

At 10 kV and at 100 kV.

Goal
Losses.
Strategy
I=P/VI=P/V, loss =I2R=I^2R.
  1. I=100 A: 1002×5=50 kWI=100\text{ A}:\ 100^2\times5=50\text{ kW}
    10 kV.
  2. I=10 A: 102×5=500 WI=10\text{ A}:\ 10^2\times5=500\text{ W}
    100 kV.
Answer5050 kW vs 500500 W.
✓ Check10× the voltage, 100× less loss ✓.
Common misconceptionMore power from step-up A transformer can't create energy: higher voltage means lower current.
Pause and think

Step-up or step-down near homes?

Summary

  • Turns ratio = voltage ratio.
  • High voltage, low current, low loss.
Key words
Step-up
More secondary turns; raises voltage.
HistoryThe War of the Currents. In the 18801880s Thomas Edison backed d.c. power, while Nikola Tesla and George Westinghouse backed a.c. Because a.c. can be transformed to high voltages for efficient long-distance transmission, a.c. won, and almost every power grid today uses it.
Fun factTransformers hum. The deep hum near a substation or a phone charger is the transformer's iron core vibrating as it's magnetised back and forth 100100 times a second on a 5050 Hz supply. In countries using 6060 Hz, the hum is slightly higher in pitch.
Keep reading for free

Create a free account to read the rest of this lesson: key formulae, worked examples, explore the graph, common mistakes, exam tip, guided practice and more. Your answers are checked and your progress is saved.